Description
BelimoD7150NL/BAC – Vanne papillon avec servomoteur, 3 voies, DN 150, Brides with Type oreilles taraudées PN 16, kvs 400 m³/h, kvmax 1100 m³/h, -20…120°C, 160 Nm, AC 24…240 V / DC 24…125 V, BACnet MS/TP, Modbus RTU, MP-Bus, 35 s, IP66/67, BorniersD7..L_BAC – Vanne papillon de régulation, à brides – 3 voies
- Torque motor 160 Nm
- Nominal voltage AC 24…240 V / DC 24…125 V
- Nominal voltage frequency 50/60 Hz
- Nominal voltage range AC 19.2…264 V / DC 19.2…137.5 V
- Power consumption in operation 20 W
- Power consumption in rest position 6 W
- Power consumption for wire sizing with 24 V 20 VA / with 230 V 52 VA
- Torque motor 160Nm
- Communicative control BACnet MS/TP Modbus RTU MP-Bus
- Operating range Y 2…10 V
- Operating range Y variable 0.5…10 V 4…20 mA
- Position feedback U 2…10 V
- Position feedback U variable 0.5…10 V
- Running time motor 35 s / 90°
- Running time motor variable 30…120 s
- Sound power level Motor 68 dB(A)
- Fluid Cold and warm water, water with glycol up to max. 50% vol.
- Fluid temperature -20…120°C
- Close-off pressure ∆ps 1200 kPa
- Differential pressure ∆pmax 300 kPa
- Flow 100% opening angle: Bypass B – AB: 70% of kvmax value; 60% opening angle: Bypass B – AB: 100% of kvs value
- Flow characteristic 0…100% opening angle: control path A–AB: S-form; Bypass B – AB: S-form inverted; 0…60% opening angle: control path A–AB: equal percentage; Bypass B – AB: equal percentage inverted
- Flow characteristic note For butterfly valve actuator combinations with the PR actuator, the flow characteristic can be set to linear using the Belimo Assistant App
- Leakage rate tight, leakage rate A (EN 12266-1)
- Pipe connectors Flange PN 16 according to ISO 7005-2
- Installation position upright to horizontal (in relation to the stem)
- Servicing maintenance-free
- Manual override hand lever
- Degree of protection IEC/EN IP66/67
- Degree of protection NEMA/UL NEMA 4X
- Enclosure UL Enclosure Type 4X
- Control pollution degree 3
- Ambient temperature -30…50°C
- Storage temperature -40…80°C
- Ambient humidity Max. 100% r.H.
Nominal voltage AC 24…240 V / DC 24…125 V
Control Open/close, modulating, communicative, hybrid for mixing and diverting applications
For water-side changeover and control applications
Communication via BACnet MS/TP, Belimo MP-Bus or conventional control
Récapitulatif technique